EFHW Transformer Turns Ratios Reference
End-Fed Half Wave (EFHW) antennas require an impedance transformer to match the high impedance of the antenna feedpoint (typically 2450–4050 Ω) to the 50 Ω output of your transceiver.
The transformer uses a specific turns ratio to achieve the desired impedance transformation ratio.
Transformer Winding Reference Table
Below is a reference table showing common winding configurations for EFHW transformers, including the resulting impedance ratios and output impedances.
| Primary Turns | Secondary Turns | Turn Ratio | Impedance Ratio | Output Impedance |
|---|---|---|---|---|
| 2 | 14 | 1:7 | 1:49 | 2450 Ω |
| 2 | 16 | 1:8 | 1:64 | 3200 Ω |
| 2 | 18 | 1:9 | 1:81 | 4050 Ω |
| 3 | 21 | 1:7 | 1:49 | 2450 Ω |
| 3 | 24 | 1:8 | 1:64 | 3200 Ω |
Understanding the Relationship
Turn Ratio
The turn ratio is simply the ratio of secondary windings to primary windings:
Turn Ratio = Secondary Turns ÷ Primary Turns
Example: 14 turns ÷ 2 turns = 1:7
Impedance Ratio
The impedance ratio is the square of the turn ratio:
Impedance Ratio = (Turn Ratio)²
Example: (1:7)² = 1:49
Output Impedance
The output impedance is calculated by multiplying the input impedance (50 Ω from your transceiver) by the impedance ratio:
Output Impedance = 50 Ω × Impedance Ratio
Example: 50 Ω × 49 = 2450 Ω
Practical Notes
Core Selection
Most EFHW transformers use ferrite toroids such as:
- FT-240-43 (larger, higher power handling)
- FT-140-43 (compact, good for QRP and portable)
- FT-114-43 (small, suitable for low power)
Most Common Configuration
The 2:14 turns (1:7 ratio / 1:49 impedance ratio) is the most widely used EFHW transformer configuration because:
- Simple to wind (fewer turns)
- Good match for typical EFHW impedance (~2450 Ω)
- Proven performance across HF bands
- Compact and efficient
Choosing the Right Ratio
- 1:49 (2:14 or 3:21) — Standard EFHW, best all-around choice
- 1:64 (2:16 or 3:24) — Higher impedance, useful for some multiband setups
- 1:81 (2:18) — Highest impedance, less common but useful in specific designs
Power Handling
Power handling depends on:
- Wire gauge used for windings
- Core size and material
- Number of turns (affects core saturation)
- Proper heat management
Always test your transformer at low power first and monitor for excessive heating.
Related Projects
This reference table applies to many antenna projects, including:
- DG1JAN UniBalun (49:1 UnUn configuration)
- xOTA antenna (49:1 and 64:1 versions)
- 221-UnUn (EFHW with WARC band links)
- Custom EFHW builds
Further Reading
- DG1JAN UniBalun Project
- DG1JAN xOTA Antenna
- ARRL Antenna Book (EFHW chapter)
73!